A G-TRAC2 MANUAL
General Manual Revised: 03/15/99
Page
15
Same as Diagram A but wider reset range because Pot
5 set at 5.
D
iagram
C
Discharge Operating Range
Absolute lowest
allowed discharge set
point
Lower reset limit
Manual Set point
Ex 70°F
Upper reset limit
Absolute highest
allowed discharge
set point
120°F48°F
Discharge Operating Range
Same as Diagram C except set point set low enough with wide reset range
so bottom end of reset is cut off by absolute lowest limit.
Discharge Operating Range
D
iagram
D
Absolute lowest
allowed discharge set
point
Lower reset
limit
Manual Set point
Ex 55°F
Upper reset limit
Absolute highest
allowed discharge
set point
120°F
48°F
Lower reset limit
same as absolute
discharge set point
Control cannot reset
into this area (below
48°F).