A SH / S-TRAC MANUAL
16 of 29 Feb 06
SORB DISTRIBUTION GRID INSTALLATION
The distribution grid is built for specific duct dimensions and air flow. Do not install the grid into any other
duct or system than it was designed for.
The duct mounting location should be in a straight length of duct and shall not be near any transitions or
elbows which could affect airflow across the grid. Do not install the grid near the outlet of a blower or
locations with high velocities. Maximum operating duct static pressure is 2.5 “w.c. (620 Pa). Higher duct
static pressures are possible, but must be indicated prior to ordering the humidifier and steam grid.
Absorption Distance
When steam first leaves the SORB distribution grid it is a hot invisible gas. As it travels into the air stream,
the steam cools and condenses into fog. The fog then evaporates into the large volume of supply air. A
very slight increase in duct air temperature will occur.
The standard duct installation absorption distance is 36” (914), beginning 8” (203) upstream of the grid.
Grid Orientation
Refer to the SORB distribution grid drawing included with the submittal records.
Duct Installations
If the duct is insulated on the inside it must be encased within a solid duct liner, and incorporate a drain
pan with a properly sized drain trap. The liner and drain pan must extend at least the length of the
absorption distance. Refer to the SORB distribution grid installation drawing included in the submittal
package.
Duct mounted grids are equipped with stainless steel adjustable mounting brackets.
Duct Mounted controls
The humidity high limit must be mounted near the top of the duct, 3 10ft (1 3m) downstream from the
distribution grid. This control is typically set between 80 and 85%RH.
An air proving device is required on all applications, and is normally located at the supply fan feeding the
duct and distribution grid.